    After calibration the manual states my door should close when I switch the Digiway to auto mode but it remains open?

    Check you have installed links between terminals 5,6 & 7 (safety sensor inputs) and the leds above 5 & 7 are lit.

  • -
    +
    I have fitted the Digiway Plus to the instructions in the manual, I have also carried out the calibration function and the indicator LED has turned green but since fitting a strike the door fails to close over the strike, what can I do?

    Firstly is the door reopening when coming to a close or is it staying closed but not locked. If the door stays closed but not locked increase ‘Approach speed’ in the ‘Advanced’ menu a small amount at a time, test a full cycle each time. If the door reopens then the Digiway is detecting the lock as an obstacle, increase the OD % again in the ‘Advanced’ menu from 2% by 1% and test run each time, increasing the OD % will disable the detection for the percentage of travel set.

  • -
    +
    Does the Digiway hold the door locked shut?

    Not on its’ own, it provides power and lock relay connections for an electrolock to be used in conjunction with the Digiway to hold the door locked shut.